高层商住楼消防给水系统设计综述摘要:针对高层商住楼的火灾危险性较大,一旦发生火灾,势必会造成不可估量的损失,本文概述了高层商住楼的火灾特点,并从消防水池、水锤、增压设施、超压等方面简述了消防给水系统设计中的问题并总结了相应的解决措施。

在一定程度上可提高高层商住楼消防给水设计水平,提高商住楼的消防安全性。

关键词:高层商住楼、火灾特点、消防给水系统、消防水池、水锤、超压Review of the design of fire water supply systems for high-rise commercial and residential buildingsAbstract: In view of the fire hazard of high-rise commercial and residential buildings, once a fire occurs, it is bound to cause immeasurable losses, this paper summarizes the fire characteristics of high-rise commercial and residential buildings, and briefly describes the problems in the design of fire water supply systems from the aspects of fire fighting pool, water hammer, pressurization facilities, overpressure, etc., and summarizes the corresponding solutions. To a certain extent, it can improve the design level of fire water supply in high-rise commercial and residential buildings and improve the fire safety of commercial and residential buildings.Keywords: high-rise commercial and residential buildings, fire characteristics, fire water supply system, fire pool, water hammer, overpressure1 引言为了适应经济的快速发展和城市人口的不断增加,我国大中城市涌现出越来越多的高层建筑,其中普通住宅和商住楼居多且发展较快[1]。

但是由于高层建筑结构复杂,内部存在相对较多的可燃物,所以高层建筑的消防压力非常大。

高层商住楼建筑高度一般为50~100m,在防火规范中属于属Ⅰ类高层建筑,在灭火设计系统设计规范中则属于危Ⅱ级,与单一的住宅楼或者商业楼相比,在进行消防给水设计时,不但需要满足消防规范的要求,还要考虑供水的科学性及合理性,避免供水浪费或是不足[2],设计难度更大。

2 高层商住楼火灾特点2.1 高层建筑火灾特点由于高层商住楼自身的楼层较多,住户层每层的住户较多,人员相对密集,发生火灾时,疏散的垂直距离较长,且只能通过楼梯逃生,疏散难度较大。

与此同时,高层建筑的消防给水需求量大,高层的供水能力不足,且我国现阶段的消防车云梯高度一般在50m左右[3],高层的火情很难得到及时的控制,所以在建高层建筑的消防给水系统是其灭火的主要方式[4]。

2.2 商住楼火灾特点根据《高规》3.0.1条,高层商住楼应属于公共建筑。

这是进行商住楼设计的一个定性指导[5]。